Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

Large diffs between 24.1.0 and 24.2.0 #10778

Open
1 of 3 tasks
jmarrec opened this issue Oct 1, 2024 · 4 comments
Open
1 of 3 tasks

Large diffs between 24.1.0 and 24.2.0 #10778

jmarrec opened this issue Oct 1, 2024 · 4 comments

Comments

@jmarrec
Copy link
Contributor

jmarrec commented Oct 1, 2024

Issue overview

This may be totally fine and justified, but I'm finding large diffs between 24.1.0 and 24.2.0 for some files, up to 40% Total Site EUI difference.

image

I'm attaching the 24.1.0 and transitioned 24.2.0 files:

large_eplus_diffs.zip

Details

Some additional details for this issue (if relevant):

  • Platform (Operating system, version): Ubuntu 24.04
  • Version of EnergyPlus (if using an intermediate build, include SHA): 24.2.0

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added
  • Ticket added to EnergyPlus Defect Complexity (Github Project)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
@Myoldmopar
Copy link
Member

I think the magnitude of those big diffs are reasonable given how many things we fixed in the central heat pump and VRF systems in this release.

@jmarrec
Copy link
Contributor Author

jmarrec commented Oct 2, 2024

image

@mjwitte
Copy link
Contributor

mjwitte commented Oct 2, 2024

@jmarrec The VRF Fan power (and related heating/cooling) changes are from these two PRs:
#10667
#10650
The VRF watercooled heat rejection, not sure, there are about 10 VRF-related PRs in 24.2

@yujiex
Copy link
Collaborator

yujiex commented Oct 2, 2024

@jmarrec the reduction in cooling might be from this #10557
The fact that heating didn't reduce as cooling might be because a similar fix of the issue where heating coil capacity not limited by OU was merged in 23.2 (#10154)

If you have the idfs for the vrf ones, I can look at what changes are the major contributors to the diffs.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
None yet
Projects
None yet
Development

No branches or pull requests

4 participants